TRMB room resistance thermometer

  • Output: Analog

Price:
Sale price112,00 EUR

Net, excl. shipping

Configuration for your inquiry

The standard version is preselected. Change only what you need — surcharges are added to your order automatically.

The source gives the range 0 … 7 but lists only seven sensors; one position remains undocumented.

Length and diameter of the sensor tube are not documented and must be requested from the manufacturer.

The class coding is unusual: Class B = 0, Class A = 5, Class AA = 2. The values are listed here in the order of the source's digits.

A transmitter is only possible in the AK082 and 1503 housings; AK061 and AK081 are not intended for it. The key itself does not block the combination.

The transmitter is a separate product with its own data sheet. TP-RTD, DTW, TH-RTD and DTW Ex only work with resistance thermometers, TP-TC only with thermocouples.

To be specified by the customer, e.g. 20 … 80 °C.

To be specified by the customer: size of the cable gland (M12, M16 or M20x1.5) and its position on one of the housing sides A to F, as well as the position of the sensor.

At this position the source lists only the digit 0, meaning “special model”.

Base price (standard version)112.00 EUR
Configured price 112.00 EUR
Questions about this product? +43 676 362 8453 office@octogon.org

Delivery Time & Shipping

Not the right fit? No problem. We build everything! Just ask.

Description

The TRMB is a room resistance thermometer with screw terminals.

It is wall-mounted and measures the air temperature in the room – in HVAC and cold storage applications. A process connection or system pressure is not required: The sensor measures the room air, the mounting position is arbitrary, and the protection class is at least IP 66. Connection is not made via a plug, but via screw terminals up to 2.5 mm² in the housing; the cable gland (M12, M16 or M20x1.5) is set according to customer specifications.

Four housings are available, allowing the design to adapt to the mounting location: three made of aluminum die-cast alloy in gray RAL 7032 – AK082 80 × 125 × 57 mm, AK081 75 × 80 × 57 mm, AK061 64 × 58 × 36 mm – and 1503 120 × 80 × 58 mm made of ABS; weights range from approximately 225 to 500 g. The sensor tube is made of stainless steel 1.4571 or Delrin POM.

Measuring elements include 1× or 2× Pt100, 1× or 2× Pt1000, 3× Pt100 or a thermocouple Type K, in 2-, 3- or 4-wire configuration and in classes A, B and AA (B1/3 DIN); the range extends from -50 … +100 °C. Without a transmitter, the resistance thermometer is connected directly to the terminals – the output is then the resistance or thermovoltage signal itself, and the sensor does not require a power supply. With a transmitter, 4 … 20 mA and 2 … 10 V are available, depending on the type, with 0.3% of the range or ±0.1% of the full scale value.

Please note before ordering: Two of the four housings do not accommodate a transmitter – it is only intended for AK082 and 1503. For the sensor tube, material and position can be selected; length and diameter are available on request. The permissible ambient temperature depends on the housing and the transmitter: Die-cast aluminum -50 … +100 °C, plastic -50 … +85 °C, with transmitter in both cases only -40 … +85 °C. The transmitters are separate products: the EKMA and EKMC suit resistance thermometers, the EKMB suits thermocouples. A declaration of conformity is available on request. The marking II 1G Ex ia IIC T6 … T4 applies only to the intrinsically safe transmitter version, not to the sensor or the housing.

Advantages at a glance

  • Four housings: die-cast aluminum AK082, AK081, AK061 or ABS 1503
  • Pt100, Pt1000, 3× Pt100 or thermocouple Type K
  • Classes A, B and AA (B1/3 DIN), 2-, 3- or 4-wire, -50 to +100 °C
  • Transmitter as an option, 4 … 20 mA or 2 … 10 V
  • Screw terminals up to 2.5 mm², cable gland M12 to M20x1.5
  • Sensor tube made of 1.4571 or Delrin POM, protection class at least IP 66

Another product?